Permitted Variations for building elements Subject to AS 1530.4 and AS 4072.1

AS 1530.4

(Formal Opinion-Assessment is not required)

AS 4072.1

(Need Formal Opinion-Assessment)

For Separation Element For Separation Element
Results from concrete or masonry elements applies to same materials within +/- 15% density Masonry and concrete construction

–        When specimen during testing fails insulation criteria on separating element, it can be calculated and increased the thickness of separating element through an opinion of registered testing authority

Results obtained from framed walls applies to

·       Concrete

·       Masonry

·       Solid gypsum blocks

Framed Wall

–        Results obtained from framed wall from one proprietary brand can be utilized for another proprietary brand through an opinion of registered testing authority

Results obtained from framed wall applies to similar wall construction with stud greater than tested wall Prefabricated walls

–        Results obtained from a pre-fabricate wall may be used to assess the performance of an alternative proprietary brands through an opinion of registered testing authority.

Results obtained from framed wall applies to same wall construction with thicker facing on with stud equal or greater to tested wall Ceiling system and ceiling/roof/floor

–        Results obtained with a suspended ceiling system of one proprietary brand may be used to assess the performance of an alternative proprietary brands through an opinion of registered testing authority.

CYBIL CONSULTS utilises the permitted variations for building elements allowed as per AS 1530.4 without looking for written assessments from NATA approved laboratories.